DEHNguard modular with integrated Backup Fuse

  • Arrester backup fuse integrated in the protection module
  • Prewired complete unit consisting of a base part and plug-in protection modules
  • Energy coordination with other arresters of the Red/Line product family
  • High discharge capacity
  • High reliability due to "Thermo Dynamic Control" SPD monitoring device
  • Easy replacement of protection modules without tools due to module locking system with module release button

meer informatie

Vergelijkbare onderwerpen

DEHNguard M TNC CI ... (FM)

Modular surge arrester with integrated backup fuses for TN-C systems with a nominal voltage of 230 / 400 V (3+0 configuration); FM version with floating remote signalling contact.

2 producten

Artikelnr. 952304 DG M TNC CI 275

GTIN 4013364128361, CCT: 85363030, Brutogewicht: 396.70 g, VPE: 1.00 Stk


Afbeeldingen

Aanvullende informatie

DEHNguard M TNC CI 275 surge arrester with backup fuses
Modular and pluggable three-pole surge arrester with integrated
backup fuse for 230/400 V TN-C systems, width: 3 modules
Type 2 SPD according to EN 61643-11
Max. continuous operating voltage: 275 V a.c.
Voltage protection level: <= 1.5 kV
Nominal discharge current: 12.5 kA
Rated breaking capacity of the integrated backup protection: 25 kA
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series
Mechanical fault indication for the arrester and integrated backup fuse


null: DG M TNC CI 275
null: 952304

Certificaten

 

Technische gegevens

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) (UC ) 275 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 12.5 kA
Max. discharge current (8/20 µs) (Imax ) 25 kA
Voltage protection level (UP ) ≤ 1.5 kV
Max. mains-side overcurrent protection not required
Approvals KEMA, VDE

Product is toegevoegd aan kladblok

Product 952304 is toegevoegd aan de winkelmand

Ga naar webshop

Artikelnr. 952309 DG M TNC CI 275 FM

GTIN 4013364128378, CCT: 85363030, Brutogewicht: 403.40 g, VPE: 1.00 Stk


Afbeeldingen

Aanvullende informatie

DEHNguard M TNC CI 275 FM surge arrester with backup fuses
Modular and pluggable three-pole surge arrester with integrated
backup fuse for 230/400 V TN-C systems, width: 3 modules
Type 2 SPD according to EN 61643-11
Max. continuous operating voltage: 275 V a.c.
Voltage protection level: <= 1.5 kV
Nominal discharge current: 12.5 kA
Rated breaking capacity of the integrated backup protection: 25 kA
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series
Mechanical fault indication for the arrester and integrated backup fuse


null: DG M TNC CI 275 FM
null: 952309

Certificaten

 

Technische gegevens

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) (UC ) 275 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 12.5 kA
Max. discharge current (8/20 µs) (Imax ) 25 kA
Voltage protection level (UP ) ≤ 1.5 kV
Max. mains-side overcurrent protection not required
Approvals KEMA, VDE
Type of remote signalling contact changeover contact

Product is toegevoegd aan kladblok

Product 952309 is toegevoegd aan de winkelmand

Ga naar webshop

DEHNguard M TNS CI ... (FM)

Modular surge arrester with integrated backup fuses for TN-S systems with a nominal voltage of 230 / 400 V (4+0 configuration); FM version with floating remote signalling contact.

2 producten

Artikelnr. 952401 DG M TNS CI 275

GTIN 4013364128347, CCT: 85363030, Brutogewicht: 500.70 g, VPE: 1.00 Stk


Afbeeldingen

Aanvullende informatie

DEHNguard M TNS CI 275 surge arrester with backup fuses
Modular and pluggable four-pole surge arrester with integrated
backup fuse for 230/400 V TN-S systems, width: 4 modules
Type 2 SPD according to EN 61643-11
Max. continuous operating voltage: 275 V a.c.
Voltage protection level: <= 1.5 kV
Nominal discharge current: 12.5 kA
Rated breaking capacity of the integrated backup protection: 25 kA
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series
Mechanical fault indication for the arrester and integrated backup fuse


null: DG M TNS CI 275
null: 952401

Certificaten

 

Technische gegevens

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) (UC ) 275 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 12.5 kA
Max. discharge current (8/20 µs) (Imax ) 25 kA
Voltage protection level [L-PE] / [N-PE] (UP ) ≤ 1.5 / ≤ 1.5 kV
Max. mains-side overcurrent protection not required
Approvals KEMA, VDE

Product is toegevoegd aan kladblok

Product 952401 is toegevoegd aan de winkelmand

Ga naar webshop

Artikelnr. 952406 DG M TNS CI 275 FM

GTIN 4013364128354, CCT: 85363030, Brutogewicht: 498.70 g, VPE: 1.00 Stk


Afbeeldingen

Aanvullende informatie

DEHNguard M TNS CI 275 FM surge arrester with backup fuses
Modular and pluggable four-pole surge arrester with integrated
backup fuse for 230/400 V TN-S systems, width: 4 modules
With remote signalling contact
Type 2 SPD according to EN 61643-11
Max. continuous operating voltage: 275 V a.c.
Voltage protection level: <= 1.5 kV
Nominal discharge current: 12.5 kA
Rated breaking capacity of the integrated backup protection: 25 kA
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series
Mechanical fault indication for the arrester and integrated backup fuse


null: DG M TNS CI 275 FM
null: 952406

Certificaten

 

Technische gegevens

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) (UC ) 275 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 12.5 kA
Max. discharge current (8/20 µs) (Imax ) 25 kA
Voltage protection level [L-PE] / [N-PE] (UP ) ≤ 1.5 / ≤ 1.5 kV
Max. mains-side overcurrent protection not required
Approvals KEMA, VDE
Type of remote signalling contact changeover contact

Product is toegevoegd aan kladblok

Product 952406 is toegevoegd aan de winkelmand

Ga naar webshop

DEHNguard M TT CI ... (FM)

Modular surge arrester with integrated backup fuses for TT and TN-S systems with a nominal voltage of 230 / 400 V (3+1 configuration); FM version with floating remote signalling contact.

2 producten

Artikelnr. 952322 DG M TT CI 275

GTIN 4013364128385, CCT: 85363030, Brutogewicht: 492.40 g, VPE: 1.00 Stk


Afbeeldingen

Aanvullende informatie

DEHNguard M TT CI 275 surge arrester with backup fuses
Modular and pluggable four-pole surge arrester with integrated
backup fuse for 230/400 V TT and TN-S systems, width: 4 modules
Type 2 SPD according to EN 61643-11
Max. continuous operating voltage: 275 V a.c.
Voltage protection level: <= 1.5 kV
Nominal discharge current: 12.5 kA
Rated breaking capacity of the integrated backup protection: 25 kA
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series
Mechanical fault indication for the arrester and integrated backup fuse


null: DG M TT CI 275
null: 952322

Certificaten

 

Technische gegevens

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) [L-N] (UC ) 275 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) [L-N] (In ) 12.5 kA
Max. discharge current (8/20 µs) [L-N] (Imax ) 25 kA
Voltage protection level [L-N] / [N-PE] (UP ) ≤ 1.5 / ≤ 1.5 kV
Max. mains-side overcurrent protection not required
Approvals KEMA, VDE

Product is toegevoegd aan kladblok

Product 952322 is toegevoegd aan de winkelmand

Ga naar webshop

Artikelnr. 952327 DG M TT CI 275 FM

GTIN 4013364128392, CCT: 85363030, Brutogewicht: 500.60 g, VPE: 1.00 Stk


Afbeeldingen

Aanvullende informatie

DEHNguard M TT CI 275 FM surge arrester with backup fuses
Modular and pluggable four-pole surge arrester with integrated
backup fuse for 230/400 V TT and TN-S systems, width: 4 modules
With remote signalling contact
Type 2 SPD according to EN 61643-11
Max. continuous operating voltage: 275 V a.c.
Voltage protection level: <= 1.5 kV
Nominal discharge current: 12.5 kA
Rated breaking capacity of the integrated backup protection: 25 kA
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series
Mechanical fault indication for the arrester and integrated backup fuse


null: DG M TT CI 275 FM
null: 952327

Certificaten

 

Technische gegevens

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) [L-N] (UC ) 275 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) [L-N] (In ) 12.5 kA
Max. discharge current (8/20 µs) [L-N] (Imax ) 25 kA
Voltage protection level [L-N] / [N-PE] (UP ) ≤ 1.5 / ≤ 1.5 kV
Max. mains-side overcurrent protection not required
Approvals KEMA, VDE
Type of remote signalling contact changeover contact

Product is toegevoegd aan kladblok

Product 952327 is toegevoegd aan de winkelmand

Ga naar webshop

DEHNguard M TN CI ... (FM)

Modular surge arrester with integrated backup fuses for single-phase 230 V TN systems (2+0 configuration); FM version with floating remote signalling contact.

2 producten

Artikelnr. 952173 DG M TN CI 275

GTIN 4013364128408, CCT: 85363030, Brutogewicht: 273.20 g, VPE: 1.00 Stk


Afbeeldingen

Aanvullende informatie

DEHNguard M TN CI 275 surge arrester with backup fuses
Modular and pluggable two-pole surge arrester with integrated
backup fuse for single-phase 230 V TN systems, width: 2 modules
Type 2 SPD according to EN 61643-11
Max. continuous operating voltage: 275 V a.c.
Voltage protection level: <= 1.5 kV
Nominal discharge current: 12.5 kA
Rated breaking capacity of the integrated backup protection: 25 kA
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series
Mechanical fault indication for the arrester and integrated backup fuse


null: DG M TN CI 275
null: 952173

Certificaten

 

Technische gegevens

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) (UC ) 275 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 12.5 kA
Max. discharge current (8/20 µs) (Imax ) 25 kA
Voltage protection level [L-PE] / [N-PE] (UP ) ≤ 1.5 / ≤ 1.5 kV
Max. mains-side overcurrent protection not required
Approvals KEMA, VDE

Product is toegevoegd aan kladblok

Product 952173 is toegevoegd aan de winkelmand

Ga naar webshop

Artikelnr. 952178 DG M TN CI 275 FM

GTIN 4013364128415, CCT: 85363030, Brutogewicht: 279.60 g, VPE: 1.00 Stk


Afbeeldingen

Aanvullende informatie

DEHNguard M TN CI 275 FM surge arrester with backup fuses
Modular and pluggable two-pole surge arrester with integrated
backup fuse for single-phase 230 V TN systems, width: 2 modules
Type 2 SPD according to EN 61643-11
Max. continuous operating voltage: 275 V a.c.
Voltage protection level: <= 1.5 kV
Nominal discharge current: 12.5 kA
Rated breaking capacity of the integrated backup protection: 25 kA
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series
Mechanical fault indication for the arrester and integrated backup fuse


null: DG M TN CI 275 FM
null: 952178

Certificaten

 

Technische gegevens

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) (UC ) 275 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 12.5 kA
Max. discharge current (8/20 µs) (Imax ) 25 kA
Voltage protection level [L-PE] / [N-PE] (UP ) ≤ 1.5 / ≤ 1.5 kV
Max. mains-side overcurrent protection not required
Approvals KEMA, VDE
Type of remote signalling contact changeover contact

Product is toegevoegd aan kladblok

Product 952178 is toegevoegd aan de winkelmand

Ga naar webshop

DEHNguard M TT 2P CI ... (FM)

Modular surge arrester with integrated backup fuses for single-phase 230 V TT and TN systems (1+1 configuration); FM version with floating remote signalling contact.

2 producten

Artikelnr. 952171 DG M TT 2P CI 275

GTIN 4013364128422, CCT: 85363030, Brutogewicht: 253.50 g, VPE: 1.00 Stk


Afbeeldingen

Aanvullende informatie

Modular and pluggable two-pole surge arrester with integrated
backup fuse for single-phase 230 V TT and TN systems, width: 2 modules
Type 2 SPD according to EN 61643-11
Max. continuous operating voltage: 275 V a.c.
Voltage protection level: <= 1.5 kV
Nominal discharge current: 12.5 kA
Rated breaking capacity of the integrated backup protection: 25 kA
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series
Mechanical fault indication for the arrester and integrated backup fuse


null: DG M TT 2P CI 275
null: 952171

Certificaten

 

Technische gegevens

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) [L-N] (UC ) 275 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) [L-N] (In ) 12.5 kA
Max. discharge current (8/20 µs) [L-N] (Imax ) 25 kA
Voltage protection level [L-N] / [N-PE] (UP ) ≤ 1.5 / ≤ 1.5 kV
Max. mains-side overcurrent protection not required
Approvals KEMA, VDE

Product is toegevoegd aan kladblok

Product 952171 is toegevoegd aan de winkelmand

Ga naar webshop

Artikelnr. 952176 DG M TT 2P CI 275 FM

GTIN 4013364128439, CCT: 85363030, Brutogewicht: 276.30 g, VPE: 1.00 Stk


Afbeeldingen

Aanvullende informatie

Modular and pluggable two-pole surge arrester with integrated
backup fuse for single-phase 230 V TT and TN systems, width: 2 modules
With remote signalling contact
Type 2 SPD according to EN 61643-11
Max. continuous operating voltage: 275 V a.c.
Voltage protection level: <= 1.5 kV
Nominal discharge current: 12.5 kA
Rated breaking capacity of the integrated backup protection: 25 kA
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series
Mechanical fault indication for the arrester and integrated backup fuse


null: DG M TT 2P CI 275 FM
null: 952176

Certificaten

 

Technische gegevens

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) [L-N] (UC ) 275 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) [L-N] (In ) 12.5 kA
Max. discharge current (8/20 µs) [L-N] (Imax ) 25 kA
Voltage protection level [L-N] / [N-PE] (UP ) ≤ 1.5 / ≤ 1.5 kV
Max. mains-side overcurrent protection not required
Approvals KEMA, VDE
Type of remote signalling contact changeover contact

Product is toegevoegd aan kladblok

Product 952176 is toegevoegd aan de winkelmand

Ga naar webshop

DEHNguard S CI ... (FM)

Pluggable single-pole surge arrester consisting of a base part and plug-in protection module; with integrated backup fuse; FM version with floating remote signalling contact.

2 producten

Artikelnr. 952079 DG S CI 275

GTIN 4013364128446, CCT: 85363030, Brutogewicht: 151.50 g, VPE: 1.00 Stk


Afbeeldingen

Aanvullende informatie

DEHNguard S CI 275 surge arrester with backup fuses
Modular and pluggable single-pole surge arrester with integrated
backup fuse, width: 1 module
Type 2 SPD according to EN 61643-11
Max. continuous operating voltage: 275 V a.c./350 V d.c.
Voltage protection level: <= 1.5 kV
Nominal discharge current: 12.5 kA
No additional backup fuse required in installations with a max. short-circuit current up to 25 kArms
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series
Mechanical fault indication for the arrester and integrated backup fuse


null: DG S CI 275
null: 952079

Certificaten

 

Technische gegevens

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) (UC ) 275 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 12.5 kA
Max. discharge current (8/20 µs) (Imax ) 25 kA
Voltage protection level (UP ) ≤ 1.5 kV
Max. mains-side overcurrent protection not required
Approvals KEMA, VDE

Product is toegevoegd aan kladblok

Product 952079 is toegevoegd aan de winkelmand

Ga naar webshop

Artikelnr. 952099 DG S CI 275 FM

GTIN 4013364128453, CCT: 85363030, Brutogewicht: 144.40 g, VPE: 1.00 Stk


Afbeeldingen

Aanvullende informatie

DEHNguard S CI 275 FM surge arrester with backup fuses
Modular and pluggable single-pole surge arrester with integrated
backup fuse, width: 1 module
With remote signalling contact
Type 2 SPD according to EN 61643-11
Max. continuous operating voltage: 275 V a.c./350 V d.c.
Voltage protection level: <= 1.5 kV
Nominal discharge current: 12.5 kA
No additional backup fuse required in installations with a max. short-circuit current up to 25 kArms
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series
Mechanical fault indication for the arrester and integrated backup fuse


null: DG S CI 275 FM
null: 952099

Certificaten

 

Technische gegevens

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) (UC ) 275 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 12.5 kA
Max. discharge current (8/20 µs) (Imax ) 25 kA
Voltage protection level (UP ) ≤ 1.5 kV
Max. mains-side overcurrent protection not required
Approvals KEMA, VDE
Type of remote signalling contact changeover contact

Product is toegevoegd aan kladblok

Product 952099 is toegevoegd aan de winkelmand

Ga naar webshop

back to top

Cookie instellingen

We gebruiken cookies om u de beste website-ervaring te kunnen bieden. Dit betreft cookies die nodig zijn voor de werking van de website, om onze zakelijke commerciële doelstellingen te beheren en andere cookies die uitsluitend worden gebruikt voor anonieme statistische doeleinden, evenals voor comfortabelere website-instellingen of voor de weergave van gepersonaliseerde inhoud. U bent vrij om te beslissen welke categorieën u wilt toestaan. Houd er rekening mee dat, afhankelijk van de instellingen die u kiest, de volledige functionaliteit van de website mogelijk niet meer beschikbaar is. Verdere informatie is te vinden in ons privacybeleid. Privacybeleid.
Als u ons toestemming hebt gegeven om cookies in te stellen, kunt u deze op elk gewenst moment intrekken door op de link "Cookie-instelling wijzigen" in de voettekst van de pagina te klikken.

  • Geef details weer Verberg details
    Noodzakelijk

    Deze cookies zijn nodig om de kernfunctionaliteiten van deze website uit te voeren, bijv. beveiligingsgerelateerde functies. Met deze cookies kunnen we ook herleiden of u ingelogd wilt blijven op uw profiel om u snel toegang tot onze diensten te bieden na het opnieuw bezoeken van onze website.

    Statistiek & Marketing

    Om onze website continu te verbeteren, volgen we anoniem gegevens voor statistische en analytische doeleinden. Met deze cookies kunnen we bijvoorbeeld het aantal bezoeken of de impact van specifieke pagina's volgen en zo onze inhoud optimaliseren.