DEHNguard ME/SE DC ... (FM)

  • Universal combined arrester / surge arrester consisting of a base part and a plug-in protection module
  • Device concept specifically developed for use in d.c. circuits
  • Powerful d.c. switching device DCD prevents fire damage caused by d.c. switching arcs
  • Use without additional backup fuse in defined applications
  • Operating state / fault indication by green / red indicator flag in the inspection window
  • Easy replacement of protection modules without tools due to module locking system with module release button

DEHNguard ME DC ... FM

Modular combined arrester for DC applications; with floating remote signalling contact.

1 Product

Artikelnr. 972146 DG ME DC Y 950 FM

GTIN 4013364347960, CCT: 85363030, Brutogewicht: 530.49 g, VPE: 1.00 Stk


Afbeeldingen

Aanvullende informatie

DEHNguard ME DC Y 950 FM combined arrester Type 1+2
3-pole, modular, plug-in combined arrester
for direct current applications, width 4 mods
Mechanical operating / fault state indication
Arrester UL approval
Type 1+2 analogous to EN 61643-11
Y circuit consisting of leakage-current-free varistor
gas discharge tube technology
DC switching device DCD specifically for use in DC current
circuits up to 950V
Max. continuous operating voltage: 950 V DC
Lightning impulse current 5kA (10/350µs)
Nominal discharge current: 12.5 kA (8/20µs)
Floating remote signalling contact as changeover contact
Vibration and shock-tested according to EN 60068


null: DG ME DC Y 950 FM
null: 972146

Certificaten

 

Technische gegevens

SPD analogous to EN 61643-11 / IEC 61643-11 type 1 + type 2 / class I + class II
Max. continuous operating voltage (d.c.) (UC ) 950 V
Lightning impulse current (10/350 µs) (Iimp ) 5 kA
Nominal discharge current (8/20 µs) (In ) 12.5 kA
Voltage protection level [DC+ -> DC-] (UP ) ≤ 4 kV
Voltage protection level [(DC+/DC-) --> PE] (UP ) ≤ 3.2 kV
Max. short circuit withstand capability (ISCCR ) 500 A / 170 ms
Approvals UL
Type of remote signalling contact changeover contact

Product is toegevoegd aan kladblok

Product 972146 is toegevoegd aan de winkelmand

Ga naar webshop

DEHNguard SE DC ...

Modular single-pole surge arrester for d.c. applications.

4 producten

Artikelnr. 972110 DG SE DC 60

GTIN 4013364158504, CCT: 85363030, Brutogewicht: 160.00 g, VPE: 1.00 Stk


Afbeeldingen

Aanvullende informatie

DEHNguard SE DC 60 surge arrester
Modular and pluggable single-pole surge arrester
for d.c. applications, width: 1.5 modules
Fault indication
Type 2 SPD according to EN 61643-11
Heavy-duty varistor technology
DCD d.c. switching device specifically for use in d.c. circuits
Max. continuous operating voltage: 60 V d.c.
Voltage protection level: <= 0.5 kV
Nominal discharge current: 12.5 kA
Short-circuit strength in case of
max. mains-side overcurrent protection (d.c.): 2000 A
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series


null: DG SE DC 60
null: 972110

Certificaten

 

Technische gegevens

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (d.c.) (UC ) 60 V
Nominal discharge current (8/20 µs) (In ) 12.5 kA
Voltage protection level (UP ) ≤ 0.5 kV
Short-circuit withstand capability without backup fuse (d.c.) (ISCCR ) 300 A
Short-circuit withstand capability for max. mains-side overcurrent protection (d.c.) (ISCCR ) 25 kA
Max. mains-side overcurrent protection 35 A gG

Product is toegevoegd aan kladblok

Product 972110 is toegevoegd aan de winkelmand

Ga naar webshop

Artikelnr. 972120 DG SE DC 242

GTIN 4013364158528, CCT: 85363030, Brutogewicht: 170.00 g, VPE: 1.00 Stk


Afbeeldingen

Aanvullende informatie

DEHNguard SE DC 242 surge arrester
Modular and pluggable single-pole surge arrester
for d.c. applications, width: 1.5 modules
Fault indication
Type 2 SPD according to EN 61643-11
Heavy-duty varistor technology
DCD d.c. switching device specifically for use in d.c. circuits
Max. continuous operating voltage: 242 V d.c.
Voltage protection level: <= 1.25 kV
Nominal discharge current: 12.5 kA
Short-circuit strength in case of
max. mains-side overcurrent protection (d.c.): 2000 A
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series


null: DG SE DC 242
null: 972120

Certificaten

 

Technische gegevens

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (d.c.) (UC ) 242 V
Nominal discharge current (8/20 µs) (In ) 12.5 kA
Voltage protection level (UP ) ≤ 1.25 kV
Short-circuit withstand capability without backup fuse (d.c.) (ISCCR ) 300 A
Short-circuit withstand capability for max. mains-side overcurrent protection (d.c.) (ISCCR ) 25 kA
Max. mains-side overcurrent protection 35 A gG

Product is toegevoegd aan kladblok

Product 972120 is toegevoegd aan de winkelmand

Ga naar webshop

Artikelnr. 972130 DG SE DC 550

GTIN 4013364158627, CCT: 85363030, Brutogewicht: 184.00 g, VPE: 1.00 Stk


Afbeeldingen

Aanvullende informatie

DEHNguard SE DC 550 surge arrester
Modular and pluggable single-pole surge arrester
for d.c. applications, width: 1.5 modules
Fault indication
Type 2 SPD according to EN 61643-11
Heavy-duty varistor technology
DCD d.c. switching device specifically for use in d.c. circuits
Max. continuous operating voltage: 550 V d.c.
Voltage protection level: <= 2.0 kV
Nominal discharge current: 12.5 kA
Short-circuit strength in case of
max. mains-side overcurrent protection (d.c.): 2000 A
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series


null: DG SE DC 550
null: 972130

Certificaten

 

Technische gegevens

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (d.c.) (UC ) 550 V
Nominal discharge current (8/20 µs) (In ) 12.5 kA
Voltage protection level (UP ) ≤ 2.0 kV
Short-circuit withstand capability without backup fuse (d.c.) (ISCCR ) 200 A
Short-circuit withstand capability for max. mains-side overcurrent protection (d.c.) (ISCCR ) 25 kA
Max. mains-side overcurrent protection 35 A gG

Product is toegevoegd aan kladblok

Product 972130 is toegevoegd aan de winkelmand

Ga naar webshop

Artikelnr. 972140 DG SE DC 900

GTIN 4013364158641, CCT: 85363030, Brutogewicht: 190.00 g, VPE: 1.00 Stk


Afbeeldingen

Aanvullende informatie

DEHNguard SE DC 900 surge arrester
Modular and pluggable single-pole surge arrester
for d.c. applications, width: 1.5 modules
Type 2 SPD according to EN 61643-11
Heavy-duty varistor technology
DCD d.c. switching device specifically for use in d.c. circuits
Max. continuous operating voltage: 900 V d.c.
Voltage protection level: <= 3.0 kV
Nominal discharge current: 12.5 kA
Short-circuit strength in case of
max. mains-side overcurrent protection (d.c.): 2000 A
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series


null: DG SE DC 900
null: 972140

Certificaten

 

Technische gegevens

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (d.c.) (UC ) 900 V
Nominal discharge current (8/20 µs) (In ) 12.5 kA
Voltage protection level (UP ) ≤ 3.0 kV
Short-circuit withstand capability without backup fuse (d.c.) (ISCCR ) 100 A
Short-circuit withstand capability for max. mains-side overcurrent protection (d.c.) (ISCCR ) 25 kA
Max. mains-side overcurrent protection 80 A gPV

Product is toegevoegd aan kladblok

Product 972140 is toegevoegd aan de winkelmand

Ga naar webshop

DEHNguard SE DC ... FM

Modular single-pole surge arrester for d.c. applications; with floating remote signalling contact.

4 producten

Artikelnr. 972115 DG SE DC 60 FM

GTIN 4013364158511, CCT: 85363030, Brutogewicht: 164.00 g, VPE: 1.00 Stk


Afbeeldingen

Aanvullende informatie

DEHNguard SE DC 60 FM surge arrester
Modular and pluggable single-pole surge arrester
for d.c. applications, width: 1.5 modules
Fault indication
Type 2 SPD according to EN 61643-11
With remote signalling contact
Heavy-duty varistor technology
DCD d.c. switching device specifically for use in d.c. circuits
Max. continuous operating voltage: 60 V d.c.
Voltage protection level: <= 0.5 kV
Nominal discharge current: 12.5 kA
Short-circuit strength in case of
max. mains-side overcurrent protection (d.c.): 2000 A
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series


null: DG SE DC 60 FM
null: 972115

Certificaten

 

Technische gegevens

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (d.c.) (UC ) 60 V
Nominal discharge current (8/20 µs) (In ) 12.5 kA
Voltage protection level (UP ) ≤ 0.5 kV
Short-circuit withstand capability without backup fuse (d.c.) (ISCCR ) 300 A
Short-circuit withstand capability for max. mains-side overcurrent protection (d.c.) (ISCCR ) 25 kA
Max. mains-side overcurrent protection 35 A gG
Type of remote signalling contact changeover contact

Product is toegevoegd aan kladblok

Product 972115 is toegevoegd aan de winkelmand

Ga naar webshop

Artikelnr. 972125 DG SE DC 242 FM

GTIN 4013364158610, CCT: 85363030, Brutogewicht: 174.00 g, VPE: 1.00 Stk


Afbeeldingen

Aanvullende informatie

DEHNguard SE DC 242 FM surge arrester
Modular and pluggable single-pole surge arrester
for d.c. applications, width: 1.5 modules
Fault indication
Type 2 SPD according to EN 61643-11
With remote signalling contact
Heavy-duty varistor technology
DCD d.c. switching device specifically for use in d.c. circuits
Max. continuous operating voltage: 242 V d.c.
Voltage protection level: <= 1.25 kV
Nominal discharge current: 12.5 kA
Short-circuit strength in case of
max. mains-side overcurrent protection (d.c.): 2000 A
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series


null: DG SE DC 242 FM
null: 972125

Certificaten

 

Technische gegevens

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (d.c.) (UC ) 242 V
Nominal discharge current (8/20 µs) (In ) 12.5 kA
Voltage protection level (UP ) ≤ 1.25 kV
Short-circuit withstand capability without backup fuse (d.c.) (ISCCR ) 300 A
Short-circuit withstand capability for max. mains-side overcurrent protection (d.c.) (ISCCR ) 25 kA
Max. mains-side overcurrent protection 35 A gG
Type of remote signalling contact changeover contact

Product is toegevoegd aan kladblok

Product 972125 is toegevoegd aan de winkelmand

Ga naar webshop

Artikelnr. 972135 DG SE DC 550 FM

GTIN 4013364158634, CCT: 85363030, Brutogewicht: 189.00 g, VPE: 1.00 Stk


Afbeeldingen

Aanvullende informatie

DEHNguard SE DC 550 FM surge arrester
Modular and pluggable single-pole surge arrester
for d.c. applications, width: 1.5 modules
Fault indication
Type 2 SPD according to EN 61643-11
With remote signalling contact
Heavy-duty varistor technology
DCD d.c. switching device specifically for use in d.c. circuits
Max. continuous operating voltage: 550 V d.c.
Voltage protection level: <= 2.0 kV
Nominal discharge current: 12.5 kA
Short-circuit strength in case of
max. mains-side overcurrent protection (d.c.): 2000 A
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series


null: DG SE DC 550 FM
null: 972135

Certificaten

 

Technische gegevens

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (d.c.) (UC ) 550 V
Nominal discharge current (8/20 µs) (In ) 12.5 kA
Voltage protection level (UP ) ≤ 2.0 kV
Short-circuit withstand capability without backup fuse (d.c.) (ISCCR ) 200 A
Short-circuit withstand capability for max. mains-side overcurrent protection (d.c.) (ISCCR ) 25 kA
Max. mains-side overcurrent protection 35 A gG
Type of remote signalling contact changeover contact

Product is toegevoegd aan kladblok

Product 972135 is toegevoegd aan de winkelmand

Ga naar webshop

Artikelnr. 972145 DG SE DC 900 FM

GTIN 4013364158658, CCT: 85363030, Brutogewicht: 194.00 g, VPE: 1.00 Stk


Afbeeldingen

Aanvullende informatie

DEHNguard SE DC 900 FM surge arrester
Modular and pluggable single-pole surge arrester
for d.c. applications, width: 1.5 modules
Fault indication
Type 2 SPD according to EN 61643-11
With remote signalling contact
Heavy-duty varistor technology
DCD d.c. switching device specifically for use in d.c. circuits
Max. continuous operating voltage: 900 V d.c.
Voltage protection level: <= 3.0 kV
Nominal discharge current: 12.5 kA
Short-circuit strength in case of
max. mains-side overcurrent protection (d.c.): 2000 A
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series


null: DG SE DC 900 FM
null: 972145

Certificaten

 

Technische gegevens

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (d.c.) (UC ) 900 V
Nominal discharge current (8/20 µs) (In ) 12.5 kA
Voltage protection level (UP ) ≤ 3.0 kV
Short-circuit withstand capability without backup fuse (d.c.) (ISCCR ) 100 A
Short-circuit withstand capability for max. mains-side overcurrent protection (d.c.) (ISCCR ) 25 kA
Max. mains-side overcurrent protection 80 A gPV
Type of remote signalling contact changeover contact

Product is toegevoegd aan kladblok

Product 972145 is toegevoegd aan de winkelmand

Ga naar webshop

back to top

Cookie instellingen

We gebruiken cookies om u de beste website-ervaring te kunnen bieden. Dit betreft cookies die nodig zijn voor de werking van de website, om onze zakelijke commerciële doelstellingen te beheren en andere cookies die uitsluitend worden gebruikt voor anonieme statistische doeleinden, evenals voor comfortabelere website-instellingen of voor de weergave van gepersonaliseerde inhoud. U bent vrij om te beslissen welke categorieën u wilt toestaan. Houd er rekening mee dat, afhankelijk van de instellingen die u kiest, de volledige functionaliteit van de website mogelijk niet meer beschikbaar is. Verdere informatie is te vinden in ons privacybeleid. Privacybeleid.
Als u ons toestemming hebt gegeven om cookies in te stellen, kunt u deze op elk gewenst moment intrekken door op de link "Cookie-instelling wijzigen" in de voettekst van de pagina te klikken.

  • Geef details weer Verberg details
    Noodzakelijk

    Deze cookies zijn nodig om de kernfunctionaliteiten van deze website uit te voeren, bijv. beveiligingsgerelateerde functies. Met deze cookies kunnen we ook herleiden of u ingelogd wilt blijven op uw profiel om u snel toegang tot onze diensten te bieden na het opnieuw bezoeken van onze website.

    Statistiek & Marketing

    Om onze website continu te verbeteren, volgen we anoniem gegevens voor statistische en analytische doeleinden. Met deze cookies kunnen we bijvoorbeeld het aantal bezoeken of de impact van specifieke pagina's volgen en zo onze inhoud optimaliseren.